Fire Stop SP 200 Application Procedure

FIRE STOP SP 200
For Openings and Cable Trays


1.Scope

Generally in industries, Fire Stop Materials are used to control and retard the transmission of fire.
Different ways are available for sealing the Openings and coating the Cables. This installation procedure covers most of these ways, therefore, for having better installation use up-to-date methods to fit specific field and service condition.

2.Usage Of Products

   - Openings (at any sizes)
   - Openings that made of concrete, masonry, steel and etc. (at any wall thickness)
   - Cable tray
   - Ladder
   - Suitable for any kind of cables, pipes, cable trays, and etc.

3.Equipment

   - Nylon brush
   - Air and Airless spray
   - Pails
   - Cutter
   - Spray nozzle 0.8 – 1.5 mm
   - Portable coating thickness gauge

4.Product Preparation

All items must be kept in closed containers and stored temperatures between +5˚C to +45˚C.Shelf life for material is 15 months if kept tightly sealed. The materials are packaged for convenience in different sizes.


5.Installation Instructions

   - Cleaning and dusting the coating's limitation of dust, oil and etc.
  - Cut the Rock Wool Panels (Density 80-150 kg/m3 and thickness 5 cm) to opening size.
   - Before using the materials, mix it for 5 minutes with low speed.
   - Coat cables in limitation of panel with Fire Stop  SP 200.
   - Coatthe rock wool panel surfaces and edges with Fire Stop  SP 200.
   - Fill the openings with rock wool panels after the curing time.
    - Fill the gaps with Fire Stop  SP 200.
   - Use the Bulk Mineral Wool to fill the gaps if required.
  -Recoat rock wool panels with Fire Stop SP 200 up to 1.5-2 mm thickness.
   - At the end coat the system with Fire Stop  SP 100 if water proofing required.


6.Curing Time

For recoating:
@ +10˚C approx 9 hours    @ +20˚C approx 8 hours    @ +30˚C approx 7 hours

Note: Using Air and Airless spray or brush depends on conditions.

7.Repair

After applying the Fire Stop materials the cables can be changed and the Fire Stop materials can be repaired.

8.Safety

Fire Stop is based on water, so it doesn't have any skin's hurt and effect on environment.


This Installation Procedures represents our best knowledge. The information given here based on our field experience. We offer this information without any guarantee.
Please check for recent date. For additional information or details contact us:

№3, 3rd floor, 549 complex, Valiasr Ave. Upon Taleghani Ave., Tehran-Iran
Tel: (+9821) 88944246, 88936166, 88949528     

Fax: (+9821) 88949529